- #Power world simulator power system analysis generator#
- #Power world simulator power system analysis simulator#
If the QV curve does not cross the x-axis, this means the system cannot solve this case. Any higher and voltage collapse would occur. This point represents the maximum increase in the load MVAR at this bus.
#Power world simulator power system analysis generator#
At some point, the MVAR value of the generator will stop decreasing and reach the “bottom” of the curve. The voltage set- point of this generator is then varied and its VAR output is allowed to be ANY value needed to meet this voltage set- point. In order to create a QV curve, a fictitious generator is placed at the bus which is being analyzed. A system is in a stable mode with respect to voltage if V – Q sensitivity is positive for every bus, and voltage unstable if V – Q sensitivity is negative for at least one bus. QV relationship shows the sensitivity and variation of bus voltages with respect to reactive power injections or absorptions. Voltage stability studies the effect of variation in reactive power on the voltage of the system. Voltage Stability Analysis using Q-V curves:
#Power world simulator power system analysis simulator#